Crown Cayman (CWI)
The Cayman Series (CWI) residential/light commercial, cast iron, hot water boiler is a fully-packaged, installer-ready product. The integral draft diverter provides a low profile design allowing the boiler to be installed in areas requiring a low clearance. This atmospheric, gas-fired boiler is for use with a conventional chimney.
The Cayman Series is packaged with the option of either natural or LP gas as well as an electronic ignition system. The Cayman Series also includes an optional tankless coil for domestic hot water (see specifications) and a larger range of available sizes.
Type: | Residential / Light Commercial |
Heat Exchanger: | Cast Iron |
Fuel: | Gas Fired (Natural or LP) |
Input: | 69 – 379 MBH* |
Efficiency (AFUE) | 81% – 83.5%** |
Venting: | Chimney |
Ignition: | Electronic Ignition |
Trim: | Water |
Domestic Water: | Optional Tankless Coil |
Burner: | N/A |
Configuration: | Packaged |
Notes: | Designed for installation on combustible floors. |
MODEL NUMBER | NO. OF SECTIONS | INPUT (MBH) |
D.O.E HEATING CAPACITY (MBH) |
IBR NET RATING (MBH) |
AFUE % |
TANKLESS HEATER (GAL/MIN) |
WATER CONTENT (GALS.) |
APPROX. SHIPPING WEIGHT (LBS) |
CWI103 | 4 | 103 | 86 | 75 | 83.1 | 2.50 | 10.0 | 432 |
CWI138 | 5 | 138 | 115 | 100 | 83.1 | 3.00 | 12.2 | 523 |
CWI172 | 6 | 172 | 144 | 125 | 83.2 | 3.50 | 14.4 | 589 |
CWI207 | 7 | 207 | 173 | 150 | 83.2 | 3.75/4.50*** | 16.6 | 669 |
CWI241 | 8 | 241 | 201 | 175 | 83.2 | 3.75/4.75*** | 18.8 | 757 |
CWI276 | 9 | 276 | 230 | 200 | 83.2 | 4.00/5.25*** | 21.0 | 839 |
CWI311 | 10 | 310 | 252 | 219 | 81.4** | 4.00/5.25*** | 23.2 | 977 |
CWI346 | 11 | 345 | 281 | 244 | 81.4** | 4.00/5.25*** | 25.4 | 1044 |
CWI380 | 12 | 379 | 309 | 269 | 81.4** | 4.00/5.25*** | 27.6 | 1125 |