Generac QT03015 30KW/27KW Liquid-Cooled Standby Generator
Type
|
Synchronous
|
Three Phase Output Alternator Leads
Single Phase Output Alternator Leads
|
6 wire
4 wire
|
(Standby Rating) Load Capacity
|
30 kW
|
Voltage regulating
|
|
Type
|
Electronic
|
Sensing
|
Single Phase
|
Regulation
|
+/- 1 percent
|
Engine
|
|
Make & Model
|
Generac Inline 4 Cylinder
|
Cylinders
|
4
|
Displacement
|
1.5 Liters
|
Bore
|
77.4 mm
|
Stroke
|
79.52 mm
|
Compression ratio
|
11 to 1
|
Lubrication
|
Oil, geared pump with filter
4 quart capacity
|
Cooling
|
Belt driven water pump, 17.7 inch fan
|
Fuel type
|
Propane, Natural Gas
|
Electrical
|
|
Battery charging alternator
|
12 Volts 30 Amps
|
Static battery charging
|
2 Amps
|
Battery recommendation
|
525CCA, Group 26
|
Voltage
|
12 Volts
|
Operation Specifications |
|||||
Output Volatge | kW | Amps |
CB Size |
||
120 / 240 Volts, 1 phase, 1 pf
120 / 208 Volts, 3 phase, 0.8 pf 120 / 240 Volts, 3 phase, 0.8 pf |
30 |
125 |
150 |
||
Fuel Consumption
Exercise cycle
25 percent rated load 50 percent rated load 75 percent rated load 100 percent rated load* For Btu, multiply ft3 / hr by 2520 (for LP) or ft3 / hr by 1000 (for NG)
|
Natural Gas
(ft3 / hr.)
60
240 320 400 492 |
Propane
(gal. / hour) ft3 / hr
0.7 24 2.6 96 3.5 128 4.4 160 5.4 197 |
|||
Engine Cooling | |||||
Air-flow (inlet air incl. alternator & combustion air)
Coolant capacity
Heat rejection – coolant
Maximu operating temp. for radiator
Maximum ambient temp. |
1800 ft3 / min. |
||||
Combustion air | Flow @ rated power 60Hz – 72 CFM | ||||
Sound Emission | Exercising @ 7 m – 59 dBA Normal operation @ 7 m – 73 dBA |
||||
Exhaust | |||||
Exhaust flow @ rated output 60Hz Exhaust temp. @ muffler outlet |
237 CFM
1130 deg. F
|
||||
Ambient conditions power adjustment | |||||
Temperature Deration
3 percent for every 10 deg. above 25 deg. C 1.65 percent for every 10 deg. above 77 deg. F
Altitude Deration
1 percent for every 100 meters above 183 meters 3 percent for every 1000 feet above 600 feet |